Technical data
|
EL1809
|
|
|
Connection technology
|
1-wire
|
|
Specification
|
EN 61131-2, type 1/3
|
|
Number of inputs
|
16
|
|
Nominal voltage
|
24 V DC (-15 %/+20 %)
|
|
“0“ signal voltage
|
-3…+5 V (EN 61131-2, type 1/3)
|
|
“1“ signal voltage
|
15…30 V (EN 61131-2, type 3)
|
|
Input current
|
typ. 3 mA (EN 61131-2, type 3)
|
|
Input filter
|
typ. 3.0 ms
|
|
|
Distributed clocks
|
–
|
|
Current consumption power contacts
|
typ. 4 mA + load
|
|
Current consumption E-bus
|
typ. 100 mA
|
|
Electrical isolation
|
500 V (E-bus/field potential)
|
|
Bit width in the process image
|
16 inputs
|
|
Configuration
|
no address or configuration setting
|
|
Conductor types
|
solid wire, stranded wire and ferrule
|
|
Conductor connection
|
solid wire conductors: direct plug-in technique; stranded wire conductors and ferrules: spring actuation by screwdriver
|
|
Rated cross-section
|
solid wire: 0.08…1.5 mm²; stranded wire: 0.25…1.5 mm²; ferrule: 0.14…0.75 mm²
|
|
Special features
|
standard input terminal with high number of channels for slow or fast 24 V DC edges, direct plug-in technique
|
|
Weight
|
approx. 65 g
|
|
Operating/storage temperature
|
-25…+60 °C/-40…+85 °C
|
|
Relative humidity
|
95 %, no condensation
|
|
Vibration/shock resistance
|
conforms to EN 60068-2-6/EN 60068-2-27
|
|
EMC immunity/emission
|
conforms to EN 61000-6-2/EN 61000-6-4
|
|
Protect. class/installation pos.
|
IP 20/variable (see documentation)
|
|
Approvals
|
CE, UL, Ex
|